The ROS2-1500 is a 2 V, 1500 Ah (10-hour rate) OPzS lead-acid battery from the Rekoser OPzS (Flooded) series. It measures 275 × 210 × 795 mm and weighs 75 kg, with M8 terminals. It stores 3 kWh and delivers up to 3000 A. The energy tank. 20+ years of proven service life. Typical applications: Solar/Wind Energy Systems, Electrical Substations, Telecommunications and Base Stations and Railway Signaling and Infrastructure.
Formerly RKS2-1500.
| Nominal Voltage | 2 V |
|---|---|
| Capacity (25ºC) | 1500 Ah (C10) |
| Energy | 3000 Wh |
| Weight | 75 kg |
| Terminal | M8 |
| Dimensions | 275 × 210 × 795 mm |
ROS2-1500
OPZS (FLOODED)Constant Discharge Ratings (A) at 25ºC
| F.V / Time | 5MIN | 10MIN | 30MIN | 1HR | 3HR | 5HR | 10HR | 20HR | 100HR |
|---|---|---|---|---|---|---|---|---|---|
| 1.90 V | 509A | 463A | 412A | 449A | 284A | 209A | 137A | 75.1A | 19.1A |
| 1.85 V | 550A | 527A | 515A | 510A | 314A | 245A | 143A | 78.4A | 20.3A |
| 1.80 V | 877A | 842A | 709A | 656A | 384A | 260A | 150A | 82.5A | 21A |
| 1.75 V | 1053A | 1010A | 811A | 731A | 398A | 267A | 155A | 86.6A | 21.5A |
Constant Discharge Ratings (W) at 25ºC
| F.V / Time | 5MIN | 10MIN | 30MIN | 1HR | 3HR | 5HR | 10HR | 20HR | 100HR |
|---|---|---|---|---|---|---|---|---|---|
| 1.90 V | 987W | 898W | 799W | 863W | 617W | 447W | 282W | 151.2W | 41.3W |
| 1.85 V | 1066W | 1023W | 968W | 981W | 645W | 497W | 306W | 164.7W | 43W |
| 1.80 V | 1702W | 1633W | 1295W | 1286W | 821W | 567W | 330W | 171.2W | 44.1W |
| 1.75 V | 2043W | 1960W | 1304W | 1296W | 869W | 593W | 344W | 175.4W | 44.5W |
ROS2-1500
OPZS (FLOODED)| Nominal Voltage | 2 V |
|---|---|
| Capacity (25ºC) | 1500 Ah (C10), 1650 Ah (C20) |
| Energy | 3000 Wh |
| Cell number | 1 |
| Charge Voltage (25°C) | Cycle use: 2.35-2.40V (-5mV/ºC/cell) Float use: 2.21-2.25V (-3mV/ºC/cell) |
| Max. Charge Current | 300 A |
| Max. Discharge Current | 3000 A |
| Internal Resistance | 0.32 mΩ |
| Self Discharge | 3 % of capacity per month at 20 °C |
| Capacity Affected by Temperature | 40 °C: 102 %, 25 °C: 100 %, 0 °C: 85 %, -15 °C: 65 % |
| Component | Material |
|---|---|
| Container | SAN |
| Cover | ABS (Flame Retardant Optional) |
| Electrolyte | Sulphuric acid |
| Negative | Lead |
| Positive | Lead dioxide |
| Safety Valve | Rubber |
| Sealant | Epoxy Resin |
| Separator | Fibre Glass |
| Terminal | Copper |
ROS2-1500
OPZS (FLOODED)To ensure optimal performance and maximize the lifespan of your REKOSER ROS2-1500 battery, follow these assembly and connection guidelines.
Before proceeding, ensure the receptacle or cabinet of your equipment complies with the unit's physical measurements:
Maintenance: Check the electrolyte level and top up only with distilled or demineralised water.
Position: Always upright.
Ventilation: Install in a ventilated room: hydrogen is released during charging.
Storage: Store charged, in a cool and dry place, and recharge periodically.
ROS2-1200 (2 V · 1200 Ah) · ROS2-2000 (2 V · 2000 Ah) · See all ROS series models