Rekoser

Maximum AGM longevity (2V). Critical infrastructure.

The RXL2-200 is a 2 V, 200 Ah (20-hour rate) AGM lead-acid battery from the Rekoser eXtended Long Life (AGM 2V) series. It measures 173 × 111 × 330 mm and weighs 13 kg, with F10 terminals. It stores 400 Wh and delivers up to 1000 A. Maximum AGM longevity (2V). Critical infrastructure. Typical applications: Railway Signaling and Infrastructure, Power Generation and UPS and Data Centers.

Formerly RKE2-200.

Main Advantages

  • Format: 2V single cells for modular configuration
  • Design Life: 20 years ultra-long life
  • Construction: Thick plates for extended service
  • Stability: Excellent performance in floating use
Nominal Voltage2 V
Capacity (25ºC)200 Ah (C20)
Energy400 Wh
Weight13 kg
TerminalF10
Dimensions173 × 111 × 330 mm
15
YEARS
LONG LIFE DESIGN
* EUROBAT CLASSIFICATION: >12 Years (Very Long Life).
2
YEARS
WARRANTY
* Subject to charge and temperature parameters stipulated in this datasheet.

Main Applications

Railway Signaling and Infrastructure
Power Generation
UPS and Data Centers

Quality Standards

CE CERTIFIEDISO 9001 / 14001GB/T19639IEC 61056JIS C8702
Rekoser

RXL2-200

EXTENDED LONG LIFE (AGM 2V)

Graphics (25°C)

Constant Discharge Ratings (A) at 25ºC

F.V / Time30MIN1HR3HR5HR10HR20HR
1.80 V161A109A49.5A34.5A20A10.5A
1.75 V167A113A51A35.6A20.1A10.6A
1.70 V171A115A51.4A35.8A20.3A10.6A
1.65 V176A118A51.7A36.1A20.3A10.7A
1.60 V180A120A52A36.3A20.4A10.7A

Constant Discharge Ratings (W) at 25ºC

F.V / Time30MIN1HR3HR5HR10HR20HR
1.80 V301W208W97W68W39.8W21W
1.75 V312W215W100W70.1W40.1W21.1W
1.70 V320W219W101W70.6W40.3W21.3W
1.65 V330W225W101W71.1W40.4W21.3W
1.60 V337W228W102W71.5W40.5W21.4W
CHARGE CHARACTERISTICS CHARGE CHARACTERISTICS
DISCHARGE CHARACTERISTIC 25oC DISCHARGE CHARACTERISTIC 25oC
SELF DISCHARGE CHARACTERISTICS SELF DISCHARGE CHARACTERISTICS
FLOAT VOLTAGE VS FLOAT LIFE FLOAT VOLTAGE VS FLOAT LIFE
Rekoser

RXL2-200

EXTENDED LONG LIFE (AGM 2V)

Specifications

Nominal Voltage2 V
Capacity (25ºC)200 Ah (C20)
Energy400 Wh
Cell number1
Charge Voltage (25°C)Cycle use: 2.35-2.40V (-3mV/C), max. Current 2.1A
Float use: 2.25-2.29V (-2mV/C)
Max. Charge Current40 A
Max. Discharge Current1000 A
Internal Resistance25 mΩ
Self Discharge3 % of capacity per month at 25 °C
Capacity Affected by Temperature40 °C: 102 %, 25 °C: 100 %, 0 °C: 85 %, -15 °C: 65 %

Construction

ComponentMaterial
ContainerABS (Flame Retardant Optional)
CoverABS (Flame Retardant Optional)
ElectrolyteSulphuric acid
NegativeLead
PositiveLead dioxide
Safety ValveRubber
SealantEpoxy Resin
SeparatorFibre Glass
TerminalCopper
Rekoser

RXL2-200

EXTENDED LONG LIFE (AGM 2V)

Quick Installation Guide

To ensure optimal performance and maximize the lifespan of your REKOSER RXL2-200 battery, follow these assembly and connection guidelines.

1. Space and Dimension Verification

Before proceeding, ensure the receptacle or cabinet of your equipment complies with the unit's physical measurements:

  • Length: 173 mm
  • Width: 111 mm
  • Height: 330 mm
  • Total Height: 364 mm
  • Weight: 13 kg
Dimensions (mm) RXL2-200

2. Terminal Configuration (F10)

3. Charge Parameters

  • Cycle use: 2.35-2.40V (-3mV/C), max. Current 2.1A
  • Float use: 2.25-2.29V (-2mV/C)
Maximum Current: Do not exceed 40 A of charge.

4. Safety and Storage

Maintenance: Sealed AGM technology, maintenance-free and leak-proof.

Position: Can be installed in any orientation, except inverted.

Storage: Store charged, in a cool and dry place, and recharge periodically.

Nearby models