Rekoser

High cyclic density in rack format for critical sites with frequent grid outages.

The RFC12-50 is a 12 V, 50 Ah (10-hour rate) AGM Deep Cycle lead-acid battery from the Rekoser Front Terminal Deep Cycle series. It measures 277 × 106 × 221 mm and weighs 17 kg, with F11 terminals. It stores 600 Wh and delivers up to 500 A. High cyclic density in rack format for critical sites with frequent grid outages. Typical applications: Telecommunications and Base Stations and Microgrids and Off-Grid Sites.

Formerly RKC12-50FT.

Main Advantages

  • Deep cycle: Built for frequent cyclic discharge
  • Front terminal: Rack integration with front access
  • Long life: EUROBAT class above 12 years
  • AGM technology: Sealed and maintenance-free
RFC12-50 – 12 V 50 Ah AGM Deep Cycle battery
Nominal Voltage12 V
Capacity (25ºC)50 Ah (C10)
Energy600 Wh
Weight17 kg
TerminalF11
Dimensions277 × 106 × 221 mm
12
YEARS
LONG LIFE DESIGN
* EUROBAT CLASSIFICATION: >12 Years (Very Long Life).
2
YEARS
WARRANTY
* Subject to charge and temperature parameters stipulated in this datasheet.

Main Applications

Telecommunications and Base Stations
Microgrids and Off-Grid Sites

Quality Standards

CE CERTIFIEDISO 9001 / 14001IEC 60896-21/22JIS C8704GB/T19639
Rekoser

RFC12-50

FRONT TERMINAL DEEP CYCLE

Graphics (25°C)

Constant Discharge Ratings (A) at 25ºC

F.V / Time15MIN30MIN1HR3HR5HR10HR20HR
10.80 V69.5A43.8A28.3A12.1A8.49A5A2.63A
10.50 V73.4A45.4A29.2A12.5A8.75A5.04A2.64A
10.20 V76A46.6A29.8A12.6A8.81A5.07A2.66A
10.02 V78.9A48A30.5A12.7A8.87A5.08A2.67A
9.60 V80.9A49A31A12.8A8.93A5.09A2.67A

Constant Discharge Ratings (W) at 25ºC

F.V / Time15MIN30MIN1HR3HR5HR10HR20HR
10.80 V763W491W322W143W100W59.7W34.8W
10.50 V806W510W333W147W103W60.1W35.4W
10.20 V834W522W339W148W104W60.5W35.5W
10.02 V866W539W348W149W105W60.7W35.6W
9.60 V888W550W353W150W105W60.8W35.8W
CHARGE CHARACTERISTICS CHARGE CHARACTERISTICS
DISCHARGE CHARACTERISTIC 25oC DISCHARGE CHARACTERISTIC 25oC
SELF DISCHARGE CHARACTERISTICS SELF DISCHARGE CHARACTERISTICS
LIFE CHARACTERISTICS OF CYCLIC USE LIFE CHARACTERISTICS OF CYCLIC USE
Rekoser

RFC12-50

FRONT TERMINAL DEEP CYCLE

Specifications

Nominal Voltage12 V
Capacity (25ºC)50 Ah (C10)
Energy600 Wh
Cell number6
Charge Voltage (25°C)Cycle use: 14.6-14.8V (-30mV/C), max. Current 2.1A
Float use: 13.6-13.8V (-20mV/C)
Max. Charge Current15 A
Max. Discharge Current500 A
Internal Resistance75 mΩ
Self Discharge3 % of capacity per month at 20 °C
Capacity Affected by Temperature40 °C: 102 %, 25 °C: 100 %, 0 °C: 85 %, -15 °C: 65 %

Construction

ComponentMaterial
ContainerABS (Flame Retardant Optional)
CoverABS (Flame Retardant Optional)
ElectrolyteSulphuric acid
NegativeLead
PositiveLead dioxide
Safety ValveRubber
SealantEpoxy Resin
SeparatorFibre Glass
TerminalCopper
Rekoser

RFC12-50

FRONT TERMINAL DEEP CYCLE

Quick Installation Guide

To ensure optimal performance and maximize the lifespan of your REKOSER RFC12-50 battery, follow these assembly and connection guidelines.

1. Space and Dimension Verification

Before proceeding, ensure the receptacle or cabinet of your equipment complies with the unit's physical measurements:

  • Length: 277 mm
  • Width: 106 mm
  • Height: 221 mm
  • Total Height: 221 mm
  • Weight: 17 kg
Dimensions (mm) RFC12-50

2. Terminal Configuration (F11)

3. Charge Parameters

  • Cycle use: 14.6-14.8V (-30mV/C), max. Current 2.1A
  • Float use: 13.6-13.8V (-20mV/C)
Maximum Current: Do not exceed 15 A of charge.

4. Safety and Storage

Maintenance: Sealed AGM technology, maintenance-free and leak-proof.

Cycling: Recharge fully after every discharge; never leave it discharged.

Position: Can be installed in any orientation, except inverted.

Storage: Store charged, in a cool and dry place, and recharge periodically.

Nearby models

RFC12-75 (12 V · 75 Ah) · See all RFC series models

Specialized Technical Support

https://rekoser.com | +34 958 04 29 73

Interested in our products?

Contact us for further information or a request for quotation

Contact