The RFC12-200 is a 12 V, 200 Ah (10-hour rate) AGM Deep Cycle lead-acid battery from the Rekoser Front Terminal Deep Cycle series. It measures 560 × 126 × 316 mm and weighs 58 kg, with M8 terminals. It stores 2.4 kWh and delivers up to 1500 A. High cyclic density in rack format for critical sites with frequent grid outages. Typical applications: Telecommunications and Base Stations and Microgrids and Off-Grid Sites.
Formerly RKC12-200FT.
| Nominal Voltage | 12 V |
|---|---|
| Capacity (25ºC) | 200 Ah (C10) |
| Energy | 2400 Wh |
| Weight | 58 kg |
| Terminal | M8 |
| Dimensions | 560 × 126 × 316 mm |
RFC12-200
FRONT TERMINAL DEEP CYCLEConstant Discharge Ratings (A) at 25ºC
| F.V / Time | 5MIN | 10MIN | 15MIN | 30MIN | 1HR | 3HR | 5HR | 10HR | 20HR |
|---|---|---|---|---|---|---|---|---|---|
| 11.10 V | 283A | 241A | 229A | 163A | 105A | 49.3A | 32.4A | 19.2A | 10A |
| 10.80 V | 331A | 267A | 251A | 173A | 108A | 51.7A | 34A | 20A | 10.5A |
| 10.50 V | 373A | 294A | 269A | 182A | 113A | 52.7A | 34.4A | 20.4A | 10.6A |
| 10.20 V | 430A | 316A | 286A | 187A | 115A | 53.6A | 34.8A | 20.6A | 10.8A |
| 10.02 V | 482A | 348A | 297A | 190A | 119A | 54.2A | 34.9A | 20.9A | 10.9A |
| 9.60 V | 540A | 378A | 304A | 192A | 121A | 54.8A | 35.5A | 21.2A | 11A |
Constant Discharge Ratings (W) at 25ºC
| F.V / Time | 5MIN | 10MIN | 15MIN | 30MIN | 1HR | 3HR | 5HR | 10HR | 20HR |
|---|---|---|---|---|---|---|---|---|---|
| 11.10 V | 533W | 457W | 436W | 315W | 203W | 96.8W | 63.8W | 38.5W | 20.1W |
| 10.80 V | 612W | 502W | 474W | 331W | 207W | 99.8W | 66.7W | 39.7W | 21.1W |
| 10.50 V | 683W | 546W | 503W | 343W | 213W | 100W | 66.9W | 40.2W | 21.2W |
| 10.20 V | 776W | 581W | 536W | 352W | 215W | 101W | 66.9W | 40.4W | 21.3W |
| 10.02 V | 858W | 633W | 563W | 363W | 222W | 102W | 67.3W | 40.6W | 21.3W |
| 9.60 V | 950W | 679W | 593W | 377W | 226W | 103W | 67.8W | 41W | 21.3W |
RFC12-200
FRONT TERMINAL DEEP CYCLE| Nominal Voltage | 12 V |
|---|---|
| Capacity (25ºC) | 200 Ah (C10) |
| Energy | 2400 Wh |
| Cell number | 6 |
| Charge Voltage (25°C) | Cycle use: 14.6-14.8V (-30mV/C), max. Current 2.1A Float use: 13.6-13.8V (-20mV/C) |
| Max. Charge Current | 50 A |
| Max. Discharge Current | 1500 A |
| Internal Resistance | 25 mΩ |
| Self Discharge | 3 % of capacity per month at 20 °C |
| Capacity Affected by Temperature | 40 °C: 102 %, 25 °C: 100 %, 0 °C: 85 %, -15 °C: 65 % |
| Component | Material |
|---|---|
| Container | ABS (Flame Retardant Optional) |
| Cover | ABS (Flame Retardant Optional) |
| Electrolyte | Sulphuric acid |
| Negative | Lead |
| Positive | Lead dioxide |
| Safety Valve | Rubber |
| Sealant | Epoxy Resin |
| Separator | Fibre Glass |
| Terminal | Copper |
RFC12-200
FRONT TERMINAL DEEP CYCLETo ensure optimal performance and maximize the lifespan of your REKOSER RFC12-200 battery, follow these assembly and connection guidelines.
Before proceeding, ensure the receptacle or cabinet of your equipment complies with the unit's physical measurements:
Maintenance: Sealed AGM technology, maintenance-free and leak-proof.
Cycling: Recharge fully after every discharge; never leave it discharged.
Position: Can be installed in any orientation, except inverted.
Storage: Store charged, in a cool and dry place, and recharge periodically.