Rekoser

Space optimisation and front-access connection for racks.

The RFT12-200 is a 12 V, 200 Ah (10-hour rate) AGM lead-acid battery from the Rekoser Front Terminal (AGM) series. It measures 522 × 238 × 218 mm and weighs 60 kg, with F12 terminals. It stores 2.4 kWh and delivers up to 1000 A. Space optimisation and front-access connection for racks. Typical applications: Telecommunications and Base Stations and UPS and Data Centers.

Formerly RKE12-200FT.

Main Advantages

  • Front terminal: Connect and measure without removing the unit
  • 19'' rack: Format designed for cabinets and racks
  • Long life: EUROBAT class above 12 years
  • AGM technology: Sealed and maintenance-free
Nominal Voltage12 V
Capacity (25ºC)200 Ah (C10)
Energy2400 Wh
Weight60 kg
TerminalF12
Dimensions522 × 238 × 218 mm
12
YEARS
LONG LIFE DESIGN
* EUROBAT CLASSIFICATION: >12 Years (Very Long Life).
2
YEARS
WARRANTY
* Subject to charge and temperature parameters stipulated in this datasheet.

Main Applications

Telecommunications and Base Stations
UPS and Data Centers

Quality Standards

CE CERTIFIEDISO 9001 / 14001GB/T19639IEC 61056JIS C8702
Rekoser

RFT12-200

FRONT TERMINAL (AGM)

Graphics (25°C)

Constant Discharge Ratings (A) at 25ºC

F.V / Time5MIN10MIN15MIN30MIN1HR3HR5HR10HR20HR
11.10 V299A271A249A177A115A51.7A34.6A19.5A10.3A
10.80 V349A301A273A187A121A53.4A35.5A20A10.5A
10.50 V395A331A293A196A125A54.5A36.4A20.4A10.7A
10.20 V454A356A316A203A127A55.3A36.8A20.7A10.9A
10.02 V509A392A334A211A130A56A37.1A20.9A11.2A
9.60 V570A425A355A221A134A56.7A37.6A21.2A11.4A

Constant Discharge Ratings (W) at 25ºC

F.V / Time5MIN10MIN15MIN30MIN1HR3HR5HR10HR20HR
11.10 V563W514W476W340W224W91.3W61.7W35W18.5W
10.80 V646W564W517W357W232W93.6W62.7W35.8W18.9W
10.50 V722W614W549W370W237W94.6W63.7W36.2W19.1W
10.20 V820W653W585W380W240W95.3W64W36.4W19.3W
10.02 V907W711W614W392W244W95.8W64.1W36.6W19.6VW
9.60 V1004W764W647W408W249W96.3W64.5W36.9W19.9W
CHARGE CHARACTERISTICS CHARGE CHARACTERISTICS
DISCHARGE CHARACTERISTIC 25oC DISCHARGE CHARACTERISTIC 25oC
SELF DISCHARGE CHARACTERISTICS SELF DISCHARGE CHARACTERISTICS
FLOAT VOLTAGE VS FLOAT LIFE FLOAT VOLTAGE VS FLOAT LIFE
Rekoser

RFT12-200

FRONT TERMINAL (AGM)

Specifications

Nominal Voltage12 V
Capacity (25ºC)200 Ah (C10), 210 Ah (C20)
Energy2400 Wh
Cell number6
Charge Voltage (25°C)Cycle use: 14.6-14.8V (-30mV/C), max. Current 2.1A
Float use: 13.6-13.8V (-20mV/C)
Max. Charge Current60 A
Max. Discharge Current1000 A
Internal Resistance25 mΩ
Self Discharge3 % of capacity per month at 25 °C
Capacity Affected by Temperature40 °C: 102 %, 25 °C: 100 %, 0 °C: 85 %, -15 °C: 65 %

Construction

ComponentMaterial
ContainerABS (Flame Retardant Optional)
CoverABS (Flame Retardant Optional)
ElectrolyteSulphuric acid
NegativeLead
PositiveLead dioxide
Safety ValveRubber
SealantEpoxy Resin
SeparatorFibre Glass
TerminalCopper
Rekoser

RFT12-200

FRONT TERMINAL (AGM)

Quick Installation Guide

To ensure optimal performance and maximize the lifespan of your REKOSER RFT12-200 battery, follow these assembly and connection guidelines.

1. Space and Dimension Verification

Before proceeding, ensure the receptacle or cabinet of your equipment complies with the unit's physical measurements:

  • Length: 522 mm
  • Width: 238 mm
  • Height: 218 mm
  • Total Height: 222 mm
  • Weight: 60 kg

2. Terminal Configuration (F12)

3. Charge Parameters

  • Cycle use: 14.6-14.8V (-30mV/C), max. Current 2.1A
  • Float use: 13.6-13.8V (-20mV/C)
Maximum Current: Do not exceed 60 A of charge.

4. Safety and Storage

Maintenance: Sealed AGM technology, maintenance-free and leak-proof.

Position: Can be installed in any orientation, except inverted.

Storage: Store charged, in a cool and dry place, and recharge periodically.

Nearby models

RFT12-190 (12 V · 190 Ah) · See all RFT series models

The same battery in other series: RHP12-200 (RHP Series – High Performance (AGM))

Specialized Technical Support

https://rekoser.com | +34 958 04 29 73

Interested in our products?

Contact us for further information or a request for quotation

Contact