RKS2-3300

OPZS

Critical Power Without Compromise

Rekoser OPzS battery. The OPzS series is a traditional tubular plate flooded battery which offers 20+ years design life according to the standard IEC60896-11.With a new design and technical improvement, it offers maximum efficiency and reliability for the widest variety of applications. This series is highly suited for all standby power applications that require the highest levels of reliability and security.

Main Advantages

Nominal Voltage2V
Capacity (25ºC) (20HR)3300Ah @ 10HR | 3465Ah @ 20HR | 4125Ah @ 100HR | 4500Ah @ 120HR
Weight (kgs)w/o electrolyte: 162
w/ electrolyte: 225 kg
TerminalF10
Dimensions (mm)576x212x771
12+
LONG LIFE DESIGN
EUROBAT
* EUROBAT CLASSIFICATION.
YEARS
WARRANTY
* Subject to charge and temperature parameters stipulated in this datasheet.

Main Applications

Quality Standards

RKS2-3300

OPZS

Graphics (25°C)

Constant Discharge Ratings (A) at 25ºC

F.V / Time 30MIN 1HR 3HR 5HR 10HR 20HR
1.80 V1932A1389A820A597A330A178A
1.75 V2128A1578A868A607A332A179A
1.70 V2219A1677A913A611A334A180A
1.65 V2364A1707A926A620A335A181A
1.60 V2412A1733A931A624A336A181A

Constant Discharge Ratings (W) at 25ºC

F.V / Time 30MIN 1HR 3HR 5HR 10HR 20HR
1.80 V3474W2552W1570W1177W657W356W
1.75 V3826W2899W1670W1196W661W359W
1.70 V3990W3081W1766W1205W667W362W
1.65 V4421W3242W1815W1221W668W362W
1.60 V4511W3292W1825W1229W669W363W
CHARGE CHARACTERISTICS flooded_battery_2v_1200ah_rks2-1200_graf1.png
DISCHARGE CHARACTERISTIC 25oC flooded_battery_2v_1200ah_rks2-1200_graf2.png
SELF DISCHARGE CHARACTERISTICS flooded_battery_2v_1200ah_rks2-1200_graf3.png
FLOAT VOLTAGE VS FLOAT LIFE flooded_battery_rks_graf4.png
CYCLE DISCHARGE VOLTAGE CURVE (Test standard BS EN 61427:2005) flooded_battery_2v_1200ah_rks2-1200_graf5.png

RKS2-3300

OPZS

Specifications

Voltage2V
Capacity (25ºC)3300Ah @ 10HR | 3465Ah @ 20HR | 4125Ah @ 100HR | 4500Ah @ 120HR
Cell number1 cells
Charge Voltage (25°C)Cycle - 2.35-2.40V (-5mV/ºC/cell)
Float - 2.20-2.24V (-3mV/ºC/cell)
Max. Charge Current825A
Max. Charge Current6000A
Internal ResistanceApprox. 0.15mOhm (fully charged @ 20°C)
Self Discharge3% of capacity declined per month at 20°C
Capacity Affected by Temperature40°C: 102%, 25°C: 100%, 0°C: 85%, -15°C: 65%

Construction

ComponentMaterial
PositiveLead dioxide
NegativeLead
ContainerSAN
CoverABS (Flame Retardant Optional)
SealantEpoxy Resin
Safety ValveRubber
TerminalCopper
SeparatorFibre Glass
ElectrolyteSulphuric acid

RKS2-3300

OPZS

  • Length: 576 mm
  • Width: 212 mm
  • Height: 771 mm
  • Weight (kgs): w/o electrolyte: 162
    w/ electrolyte: 225 kg

Terminales F10

  • Cycle - 2.35-2.40V (-5mV/ºC/cell)
  • Float - 2.20-2.24V (-3mV/ºC/cell)

Specialized Technical Support

Rekoser offers consulting services for the dimensioning of critical systems, racks, battery monitoring.

https://rekoser.com | +34 958 04 29 73