AGM Battery. Rekoser stationary series, general use, has been specially designed to optimize its life and quality, minimizing maintenance and maximizing self discharge of their properties for longer storage. RKE series is ideal for security and alarm systems, UPS systems,emergency light systems and other small backup applications.

Main Advantages

  • AGM Technology: Fully sealed, maintenance-free, and leak-proof.
  • High Energy Density: Optimized for critical and rapid discharges.
  • Low Self-Discharge: Pb-Ca alloy allows for long storage periods.
  • Advanced Safety: Safety valves and reinforced ABS container.
Nominal Voltage12V
Capacity (25ºC) (20HR)110Ah @ 10HR
Weight (kgs)32.5 kg
TerminalF14
Dimensions (mm)395x110x285
12+
LONG LIFE DESIGN
EUROBAT
* EUROBAT CLASSIFICATION.
2
YEARS
WARRANTY
* Subject to charge and temperature parameters stipulated in this datasheet.

Main Applications

UPS Systems
Security
Telecom
Medical Equipment
Solar Energy
Emergency

Quality Standards

CE CERTIFIEDISO 9001 / 14001IEC 61056JIS C8704GB/T19639

RKE12-110FT

AGM GENERAL PURPOSE

Graphics (25°C)

Constant Discharge Ratings (A) at 25ºC

F.V / Time 15MIN 30MIN 1HR 3HR 5HR 10HR 20HR
9.60 V178A108A68.2A28.1A19.6A11.2A5.88A
10.02 V174A106A67.2A27.9A19.5A11.2A5.87A
10.20 V167A102A65.5A27.7A19.4A11.1A5.85A
10.50 V162A99.9A64.2A27.5A19.3A11.1A5.82A
10.80 V153A96.3A62.2A26.7A18.7A11.0A5.78A

Constant Discharge Ratings (W) at 25ºC

F.V / Time 15MIN 30MIN 1HR 3HR 5HR 10HR 20HR
9.60 V1953W1210W777W330W232W134W70.5W
10.02 V1906W1185W776W328W231W133W70.4W
10.20 V1836W1149W746W326W229W133W70.2W
10.50 V1773W1121W732W323W228W132W69.8W
10.80 V1680W1080W709W314W221W131W69.3W
CHARGE CHARACTERISTICS agm_battery_12v_7ah_rke12-7_graf1.png
DISCHARGE CHARACTERISTIC 25oC agm_battery_12v_7ah_rke12-7_graf2.png
SELF DISCHARGE CHARACTERISTICS agm_battery_12v_7ah_rke12-7_graf3.png
FLOAT VOLTAGE VS FLOAT LIFE agm_battery_12v_7ah_rke12-7_graf4.png

RKE12-110FT

AGM GENERAL PURPOSE

Specifications

Voltage12V
Capacity (25ºC)110Ah @ 10HR
Cell number6 cells
Charge Voltage (25°C)Cycle - 14.6-14.8V (-30mV/C), max. Current 2.1A
Float - 13.6-13.8V (-20mV/C)
Max. Charge Current30A
Max. Charge Current800A
Internal ResistanceFully Charged 25 m Ω
Self Discharge3% of capacity declined per month at 20°C
Capacity Affected by Temperature40°C: 102%, 25°C: 100%, 0°C: 85%, -15°C: 65%

Construction

ComponentMaterial
PositiveLead dioxide
NegativeLead
ContainerABS (Flame Retardant Optional)
CoverABS (Flame Retardant Optional)
SealantEpoxy Resin
Safety ValveRubber
TerminalCopper
SeparatorFibre Glass
ElectrolyteSulphuric acid

RKE12-110FT

AGM GENERAL PURPOSE

Quick Installation Guide

To ensure optimal performance and maximize the lifespan of your REKOSER RKE12-110FT battery, follow these assembly and connection guidelines.

1. Space and Dimension Verification

Before proceeding, ensure the receptacle or cabinet of your equipment complies with the unit's physical measurements:

  • Length: 395 mm
  • Width: 110 mm
  • Height: 285 mm
  • Weight (kgs): 32.5 kg

2. Terminal Configuration (F14)

Terminales F14
  • Terminals: Ensure your system's connectors match the F14 type to prevent electrical arcing.
  • Polarity: The ABS (UL94-HB) container has high-visibility markings to prevent short circuits.

3. Initial Charge Parameters

  • Cycle - 14.6-14.8V (-30mV/C), max. Current 2.1A
  • Float - 13.6-13.8V (-20mV/C)
Maximum Current: Do not exceed 30A of charge.

4. Safety and Storage Recommendations

Maintenance: Sealed AGM technology, maintenance-free, and leak-proof.

Position: Can be installed in any orientation (except inverted).

Storage: Low self-discharge (3% of capacity declined per month at 20°C). Pb-Ca alloy for long periods at ~25°C.

Specialized Technical Support

Rekoser offers consulting services for the dimensioning of critical systems, racks, battery monitoring.

https://rekoser.com | +34 958 04 29 73

Interested in our products?

Contact us for further information or a request for quotation

Contact