Batería NiCd de Rekoser son especiamente recomendadas para ferrocarriles y telecomunicaciones
| Voltaje Nominal | 1.2V |
|---|---|
| Capacidad (25ºC) (20HR) | 120Ah @ 5HR |
| Peso (kgs) | 8.5Kg kg |
| Terminal | Nickel- Clad Steel |
| Dimensiones (mm) | 165mmx105mmx300mm |
Ratios de descarga constante (A) at 25ºC
| F.V / Time | 1SEC | 5SEC | 1MIN | 1.5MIN | 5MIN | 1HR |
|---|---|---|---|---|---|---|
| 1.14 V | 714A | 667A | 443A | 378A | 332A | 109A |
| 1.10 V | 776A | 738A | 573A | 465A | 352A | 85A |
| 1.0 V | 1025A | 978A | 842A | 635A | 518A | 116A |
Ratios de descarga constante (W) at 25ºC
| F.V / Time | 1SEC | 5SEC | 1MIN | 1.5MIN | 5MIN | 1HR |
|---|---|---|---|---|---|---|
| 1.14 V | W | W | W | W | W | W |
| 1.10 V | W | W | W | W | W | W |
| 1.0 V | W | W | W | W | W | W |
| Voltaje | 1.2V |
|---|---|
| Capacidad (25ºC) | 120Ah @ 5HR |
| Número de células | |
| Voltaje de carga (25°C) | Cycle - 1.0-1.2V Float - 1.38V +-0.01V |
| Corriente máx. de carga | |
| Corriente máx. de carga | |
| Resistencia Interna | Approx. 0.00034-0.00036 Ω |
| Autodescarga | >=120Ah 1 month |
| Capacidad afectada por la temperatura | 40°C: 102%, 20°C: 100%, 0°C: 90%, -18°C: 80% |
| Componente | Material |
|---|---|
| Positivo | Nickel oxide-hydroxide |
| Negativo | Cadmium |
| Contenedor | ABS/PP |
| Tapa | ABS/PP |
| Sellador | - |
| Válvula de seguridad | Rubber |
| Terminal | Nickel- Clad Steel |
| Separador | - |
| Electrolito | Potassium Hydroxide |
Rekoser ofrece servicios de consultoría para el dimensionamiento de sistemas críticos, racks y monitorización de baterías.
https://rekoser.com | +34 958 04 29 73Contáctanos para mayor información o solicitar una cotización
Contactar